Characteristic | Useage | ||||||
●Low internal resistance | ●High power pulse demand | ||||||
●Fast charge and discharge | ●Wind power pitch | ||||||
●RoHS certification | ●Grid distribution terminal | ||||||
●UL certification | ●Small UPS | ||||||
●Long life | ●start-stop system |
SSP series technical indicators
Project | Characteristic | |||||||
Operating temperature | -40℃ to +65℃@2.7V | |||||||
-40℃ to +80℃@2.3V | ||||||||
Storage temperature | -40℃ to +70℃ | |||||||
Capacity | 100~600F | |||||||
Capacity gap | -10% to +30% | |||||||
Rated voltage | 2.7VDC | |||||||
Surge voltage | 2.85VDC | |||||||
temperature characteristics | From -40℃ to 65℃ | |||||||
Capacity change: ΔC < 20% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
High temperature load life | Load ≤ 1000 h under operating temperature and rated voltage | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Normal temperature load life | 10 years under load at 25℃ and rated voltage | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Normal temperature cycle life | At 25℃, after 500,000 charge-discharge cycles (from rated voltage to 1/2 rated voltage) | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Storage life | It can be placed for two years without load in the environment of 25 ℃ to meet the requirements of high temperature load life | |||||||
Steady-state damp heat | 40℃, 90%RH and rated voltage, load 240h, meet high temperature load life requirements |
SIZE:
List of SSP series standard products
SSQ series technical indicators
Project | Characteristic | |||||||
Operating temperature | -40℃ to +85℃ | |||||||
Storage temperature | -40℃ to +85℃ | |||||||
Capacity | 100~500F | |||||||
Capacity gap | -10% to +30% | |||||||
Rated voltage | 2.7VDC | |||||||
Surge voltage | 2.85VDC | |||||||
temperature characteristics | From -40℃ to 85℃ | |||||||
Capacity change: ΔC < 20% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
High temperature load life | Load ≤ 1000 h under operating temperature and rated voltage | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Normal temperature load life | 10 years under load at 25℃ and rated voltage | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Normal temperature cycle life | At 25℃, after 500,000 charge-discharge cycles (from rated voltage to 1/2 rated voltage) | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Storage life | It can be placed for two years without load in the environment of 25 ℃ to meet the requirements of high temperature load life | |||||||
Steady-state damp heat | 40℃, 90%RH and rated voltage, load 240h, meet high temperature load life requirements |
SIZE:
List of SSQ series standard products
SSE series technical indicators
Project | Characteristic | |||||||
Operating temperature | -40℃ to +65℃@2.7V | |||||||
-40℃ to +80℃@2.5V | ||||||||
Storage temperature | -40℃ to +70℃ | |||||||
Capacity | 100~500F | |||||||
Capacity gap | -10% to +30% | |||||||
Rated voltage | 3.0VDC | |||||||
temperature characteristics | From -40℃ to 65℃ | |||||||
Capacity change: ΔC < 20% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
High temperature load life | Load ≤ 1000 h under operating temperature and rated voltage | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Normal temperature load life | 10 years under load at 25℃ and rated voltage | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Normal temperature cycle life | At 25℃, after 500,000 charge-discharge cycles (from rated voltage to 1/2 rated voltage) | |||||||
Capacity change: ΔC < 30% of initial measurement @ 25℃ | ||||||||
Internal resistance change: ΔESR < 100.00% of nominal | ||||||||
Storage life | It can be placed for two years without load in the environment of 25 ℃ to meet the requirements of high temperature load life | |||||||
Steady-state damp heat | 40℃, 90%RH and rated voltage, load 240h, meet high temperature load life requirements |
SIZE:
List of SSE series standard products